Latest Rockwell Automation vulnerabilities #
Rockwell Automation has disclosed a vulnerability in their ControlLogix 5580, Guard Logix 5580, CompactLogix 5380, and 1756-EN4TR products.
CVE-2024-3493 is rated high with CVSS score of 8.6 involves a specific malformed fragmented packet type which can cause a major nonrecoverable fault (MNRF) in Rockwell Automation’s ControlLogix 5580, Guard Logix 5580, CompactLogix 5380, and 1756-EN4TR. If exploited, the affected product will become unavailable and require a manual restart to recover it.
What is the impact? #
Successful exploitation of these vulnerabilities result in devices becoming inaccessible remotely and crashing and then require manual intervention to restart them.
Are updates or workarounds available? #
Rockwell Automation has provided software updates for the impacted versions.
| Affected Product | First Known in Firmware Revision | Corrected in Firmware Revision |
| ControlLogix® 5580 | V35.011 | V35.013, V36.011 |
| GuardLogix 5580 | V35.011 | V35.013, V36.011 |
| CompactLogix 5380 | V35.011 | V35.013, V36.011 |
| 1756-EN4TR | V5.001 | V6.001 |
How do I find potentially vulnerable systems with runZero? #
From the Asset Inventory, use the following query to locate systems running potentially vulnerable software:
hw:"1756-EN4TR"Rockwell Automation PowerFlex 527 vulnerabilities (March 2024) #
In March 2024, Rockwell Automation disclosed multiple vulnerabilities in their PowerFlex 527 product.
CVE-2024-2425 and CVE-2024-2426 are both rated high with CVSS score of 7.5 and both involve improper input validation which could cause a web server to crash and CIP communication disruption, respectively, which leads to requiring manual restarts.
CVE-2024-2427 is rated high with CVSS score of 7.5 and indicates a denial-of-service scenario due to improper network packet throttling which causes a device to crash and require a manual restart.
What was the impact? #
Successful exploitation of these vulnerabilities result in devices becoming inaccessible remotely and crashing and then require manual intervention to restart them.
Are updates or workarounds available? #
Rockwell Automation does not currently have a fix for these vulnerabilities. Users of the affected software are encouraged to apply risk mitigations and security best practices, where possible.
Users should disable the web server if it is not needed, which should be disabled by default. Additionally, users should ensure these devices are isolated in their own networks to prevent unwanted packets flooding the device.
How do I find potentially vulnerable systems with runZero? #
From the Asset Inventory, use the following query to locate systems running potentially vulnerable software:
hw.product:"powerflex"About Version 2 Digital
Version 2 Digital is one of the most dynamic IT companies in Asia. The company distributes a wide range of IT products across various areas including cyber security, cloud, data protection, end points, infrastructures, system monitoring, storage, networking, business productivity and communication products.
Through an extensive network of channels, point of sales, resellers, and partnership companies, Version 2 offers quality products and services which are highly acclaimed in the market. Its customers cover a wide spectrum which include Global 1000 enterprises, regional listed companies, different vertical industries, public utilities, Government, a vast number of successful SMEs, and consumers in various Asian cities.
About runZero
runZero, a network discovery and asset inventory solution, was founded in 2018 by HD Moore, the creator of Metasploit. HD envisioned a modern active discovery solution that could find and identify everything on a network–without credentials. As a security researcher and penetration tester, he often employed benign ways to get information leaks and piece them together to build device profiles. Eventually, this work led him to leverage applied research and the discovery techniques developed for security and penetration testing to create runZero.